Product Introduction
F96-WNJ-Ⅱ Power Meter with Reverse Power Relay. Wide-angle models: F96-WNJ, Q96-WTCZAN; Right-angle models: F96-WNJB, Q96-WTCAN. Specifications: -15-100KW (Custom sizes available). Inquire for details.
Specifications
F96-WNJ-Ⅱ Power Meter with Reverse Power Relay
Wide Angle Models: F96-WNJ Q96-WTCZAN
Right Angle Models: F96-WNJB Q96-WTCAN
Specifications: -15-100KW (Customizable specifications available) Inquire for details
Power Meter with Reverse Power Relay Alarm Function
Features
1. Multifunctional instrument integrating three-phase power measurement and indication, reverse power measurement, and electrical functions; suitable for power measurement in marine power grids.
2. Accuracy: 1.5 class
3. Ambient Temperature: -25℃~+55℃
4. Enclosure Protection: IP42
5. Vibration Resistance: 2-200Hz, ≤0.7g
6. Withstand Voltage: AC2.5KV, 50Hz, 1min
7. Power Consumption: ≤3VA
8. Output Contact Capacity: AC250V 1A; DC28V 1A
9. Reverse power amplitude setting: -0…-25%×P (Customers can set this according to their own requirements)
10. Delay time setting: 0.4…30s (Customers can set this according to their own requirements)
11. Measurement range: Same as F96-W
| Model Number | Development Angle | Overall Dimensions (mm) | Opening Size (mm) | Weight (Kg) |
| F96-WNJB | 90° | 96×96×115 | 92×92+0.5 | 0.6 |
| F96-WNJ | 240° | 0.9 |
Instructions for Use
1. When the power is connected, the green indicator light illuminates, indicating that the instrument is in working condition.
2. When the reverse power exceeds the set point, the ****** indicator light (-P) illuminates. After the set time delay, the red indicator light (RELAY) illuminates, indicating that the relay is likely to activate and change state.
3. The reverse power relay has an inverse time characteristic.
4. For special purpose instruments, please add "J" after the first half of the model number (only applicable to 240° instruments).